Daikin

  Silencer for circular ducts LDC
 


The silencer is very easy to install and gives a high performance. It is possible to connect two pieces together which will result in an extremely good noise suppression. The perfect condition will be if the fan used is type KVK or KVKE.

 

 

  Technical data
 
Type Length
(mm)
Ø di
(mm)
Ø d0
(mm)
Weight
(kg)
Suppression dB Frequency band Hz
125 250 500 1 K 2 K 4 K 8 K
LDC 100-600 600 100 200 4.1 8 14 26 34 41 45 25
LDC 125-600 600 125 224 4.5 6 12 22 28 37 38 22
LDC 125-900 900 125 224 7.6 9 18 30 40 48 43 24
LDC 160-600 600 160 260 5.8 5 10 18 23 33 30 19
LDC 160-900 900 160 260 9.0 8 16 27 36 47 37 21
LDC 200-600 600 200 315 7.0 4 9 17 22 29 25 18
LDC 200-900 900 200 315 10.0 7 13 24 31 44 31 20
LDC 250-900 900 250 355 12.2 6 11 21 27 39 25 19
LDC 315-900 900 315 450 15.0 5 9 18 23 32 20 18
LDC 400-900 900 400 630 41.0 5 8 11 23 19 17 15
 